The system detects Partial Discharge Signal, generated when Gas Insulated
Switchgear (GIS) has troubles, with Ultra High Frequency (UHF) Sensor, and it
is monitoring and diagnosing troubles by On-line.
|
Item
|
Description
|
Remark
|
|
Power Supply
|
AC90~240V(60Hz)
|
Band- fixed
|
|
Detection
frrequency
|
500Mhz~1,500Mhz
|
|
|
Minimum
detection signal
|
-55dBm(=0.0032µW)
|
|
|
Over voltage
protection
|
Built-in Surge Protector
|
|
|
Input channel
|
Simultaneous measurement on 8Ch. (Sensor)
|
N-Type Connector
|
|
Communication
with Server
|
TCP/IP(Lan) or Optical Fiber selectable
|
|
|
Indication
|
Indicates Local Unit operation status(Monitoring, Real
Time Mode) Power and communication status
|
|
|
Calibration
|
8Ch.(Calibration Pulse)
*Separate Calibration Unit used
|
SMA type connector
|
|
Synchrorized signal
|
3Ch.(A phase, B phase, C phase)
(either inner sync or outer sync selectable)
|
Terminal block
|
|
Input signal sensitivity
|
-60dBm(Min.) ~ 10dBm(max.)
|
|
|
Gain
|
Remote control from server
Adjustable from 5 steps(1, 2, 4, 8, 16)
Basic 83dB(1step)
|
|
|
Filter
|
Remote control frim server
Adjustable from 3 kinds
|
|
|
Operation
|
DSP Dual(600Mhz)
|
|
|
Sampling
|
8Mbyte/Sec
|
|
|
System construction diagram

|
|
Section
|
Contents
|
Remark
|
|
Power
|
|
|
|
Detection Area
|
|
|
|
Min. Detection Signal
|
|
|
|
Over Voltage Protection
|
Surge Protector Built-in
|
|
|
Input Channel
|
|
|
|
Communication with Server
|
|
|
|
Display
|
LCD (20 x 4) - Local Unit displays the
status of operation
LED (Power, Rx, Tx, Sync) - Power,
Communication, Synchronous Signal
Server Data Analysis, Remote Control,
Save
|
|
|
Calibration
|
8 Ch. (Calibration Pulse)
- Use an extra Calibration Unit
|
|
|
Synchronous Signal
|
3 Ch. (A Phase, B Phase, C Phase)
- Internal & external synchronous
|
|
|
Input Sensitivity
|
60dBm (Min.) ~ 10dBm(Max.)
|
|
|
Gain
|
Remote-controlled by Server
5 Steps (1,2,4,8,16)
Basically 83dB (1 Step)
|
|
|
Filter
|
Remote-controlled by Server
3 Steps selectable
|
Minimize a field noise effect
|
|
Operation
|
|
|
|
Sampling
|
|
|
|
Withstand Voltage
|
10KV/min Strength
|
|
|
Data Gain Unit
|
Watch Dog(H/W, S/W) (Built-in)
|
|
|
Dynamic Test
|
Suitable for Vibration-Resistance,
Impact - Resistance
|
|
|
External Case
|
|
Waterproof
|
|
EMC
|
Applied to Industrial Emission Standard
|
|